33 YONGE STREET

DESIGN CRITERIA MANUAL

 

 

 

 

 

 



INTRODUCTION

The Design Criteria Manual is prepared to assist our valued Tenants in the design and construction of leasehold improvements before, during and after the substantial completion of the base building project.  Revisions, as the nature of the project’s site conditions change, will be supplemented.

This manual contains information about policies, procedures, and requirements established by the Landlord for Tenants who undertake improvements within the leased premises; it also outlines the basic design specifications for the building.  The information provided within applies as a general rule and should be made available to the Tenant's Designers and Contractors, who are urged to acquaint themselves thoroughly with the material herein, as it will form the basis of the Landlord's approval for all Tenant submissions.

The Landlord's approval of all drawings is for the purpose of obtaining information about the intended design and use of the premises and the impact such a design and use may have on the base building systems, structurally, electrically and mechanically.

By granting such approval the Landlord is not reviewing or agreeing with any Consultants’ design accuracy; rather, only approving or disapproving of the impact on the base building systems.

It is recommended that the Tenant and/or Designer visit the site to review and verify all site conditions prior to the preparation of design work.

The Landlord reserves the right to amend, add or delete the information in the manual at any time and the Tenant is obliged to abide by such changes upon notification thereof.  All costs associated with the compliance shall be at the Tenant's expense.

This manual is intended to reflect only standard conditions or situations and does not amend the formal lease agreement, which is to govern in the event of any inconsistencies.

Permission to deviate from the Design Criteria Manual must be obtained in writing.  Notes on drawings in conflict with the design criteria have no validity.


SECTION I

INFORMATION, PROCEDURES, AND REGULATIONS


1.        TENANT CO-ORDINATION

The primary functions of the Construction Services Project Manager, as the Landlord's representative, are:

a.      To provide guidance and assistance to Tenants during both the design and construction phases of their leasehold improvements;

 

b.      To review and comment upon all Tenant submissions before work begins with the leased premises; and,

 

c.      To provide liaison between and among the Landlord, Landlord's Contractor and Consultants, the Tenant's Contractor and Designer.

The following individuals can provide answers to any questions, comments and submissions:

PAUL MILBURY

 

Manager, Technical Services

GWL Realty Advisors Inc.

33 Yonge Street, Suite 418

Toronto, Ontario

M5E 1G4

HEIDI LABRASH

 

Sr. Property Manager

GWL Realty Advisors Inc.

33 Yonge Street, Suite 418

Toronto, Ontario

M5E 1G4

(T)       416 363 3231

(F)       416 363 1483

(T)       416 363 9845

(F)       416 363 1483

 

 

 

 


2.        LANDLORD'S BASE BUILDING CONSULTANTS

STRUCTURAL CONSULTANTS

TELECOMMUNICATIONS

Halcrow Yolles

163 Queen Street East

Toronto, Ontario

M5A 1S1

 

Telephone       416 363 8123

Fax:                 416 363 0341

Contact:          Mr. Gary Moloney

Netricom

20 Dovedale Court

Scarborough, Ontario

M1S 5A7

 

Telephone:      416 285 4403

Fax:                 416 288 9473

 


 

MECHANICAL CONSULTANTS

BUILDING CODE & FIRE PROTECTION CONSULTANTS

 

Hidi Rae Consulting

1 Yonge Street, Suite 2100

Toronto, Ontario

M5E 1E5

 

Telephone       416 364 2100

Fax:                 416 364 2276

Contact:          Mr. Kaz Swiderski

Larden Muniak Consulting Inc.

4195 Dundas Street West, Suite 233

Toronto, Ontario

M8X 1Y4

 

Telephone       416 762 3808 ext. 227

Fax:                 416 762 7746

Contact:          Ms. Amy Pothier

 

 

ELECTRICAL CONSULTANTS

 

Mulvey + Banani

44 Mobile Drive

Toronto, Ontario

M4A 2P2

 

Telephone:      416 751 2520

Fax:                 416 751 1430

Contact:          Mr. Rob Marcuzzi

 

Hidi Rae Consulting

1 Yonge Street, Suite 2100

Toronto, Ontario

M5E 1E5

 

Telephone:      416 364 2100

Fax:                 416 364 2276

Contact:          Mr. Kaz Swiderski

 

ARCHITECTURAL CONSULTANTS

 

Comley Van Brussel

2600 Skymark Avenue, Building 8, Unit 101

Mississauga, Ontario

L4W 5B2

 

Telephone       416 621 7745

Fax:                 905 602 8720

Contact:          Mr. Angelo Gatti

Gio Tan Design Associates

365 Bloor Street East, Suite 1003

Toronto, Ontario

M4W 3L4

 

Telephone:      416 285 4403

Fax:                 416 288 9473

Contact           Ms. Patricia Rynkun


3.        REGULATORY BODIES

The Tenant is required to design and construct its improvements in accordance with any and all applicable Building Codes, By-Laws, and directives of all governing authorities.  The Tenant is also required to secure its own Building Permit and all other approvals required by law.  Building Permits may be obtained at:

 

Department of Building & Inspections

City Hall - 15th Floor, East Tower

100 Queen Street West

Toronto, Ontario

M5H 2N2

4.        TENANT DESIGN AND WORKING DRAWINGS

To assist the Tenant in the production of working drawings, the Landlord (upon request) can provide the Tenant with any available drawings of the leased premises indicating the major elements of the base building structure and its systems.  Any additional drawings or information the Tenant may reasonably require for this purpose may be obtained through the Property Management Office or by surveying existing site conditions.

4.1              Tenant Consultants

 

4.1.1     The Tenant shall engage all the Architects, Engineers and Certified Designers, collectively with the Tenant Consultants to prepare dimensioned construction drawings and specifications, which are necessary for the construction of the Tenant's leasehold improvements.  The Landlord, during his review process, will use the base-building consultants.  Landlord, from time to time, may require the Tenant to produce additional or more detailed drawings or information, which in the Landlord's opinion may be necessary to identify and describe the nature of the intended improvements.  Any added cost for either or both of these requirements would be at the Tenant's expense.

 

4.1.2     The Tenant shall make themselves familiar with the by-law and code requirements as well as this Design Criteria Manual, before preparing the plans and specifications.

 

4.1.3     By giving approval to such plans, the Landlord and his consultants do not waive the Tenant's responsibility to ensure that any and all Tenant improvements meet the requirements of the Lease, this Design Criteria Manual, or relevant and applicable Building Codes.  Furthermore, any construction deficiencies, H.V.A.C., airflow problems, etc., are the responsibilities of the Tenant and their respective contractor(s).  The Landlord's review of the drawings is only to ensure that the Tenant's design does not negatively impact the building's systems or aesthetics.

 

4.2              Approval of Tenant Drawings Submission of Preliminary Drawings

 

4.2.1        The Tenant shall submit two (2) prints of preliminary drawings and one (1) digital set showing the proposed office layout for the preliminary approval of the Landlord, which will be given within 10 business days of receipt of the submitted drawings.  The preliminary drawings will be checked from the standpoint of physical compatibility and any problems encountered shall be returned to the Tenant for resolution.  If required, the Tenant shall revise the preliminary drawings and resubmit them showing the proposed resolution to the Landlord's concerns, for approval.  The Tenant shall provide total heating and cooling capacity calculations for verification to base building capacity.

 

4.2.2        The Tenant shall submit one (1) digital and two (2) copies of complete working drawings and specifications for final approval by the Landlord, which will be given within 10 business days of receipt of the submitted drawings in accordance with the Construction Procedures contained in the Lease and prior to the commencement of the fixturing period.  Electrical, mechanical and structural drawings must be signed and sealed by an Engineer (responsible for the design) licensed to practice Engineering in the Province of Ontario.

Tenant drawings shall consist of:

1.            Floor Plans

 

Floor plans should have a drawing scale of 1:100 (metric) or 1/8" = 1'-0" (imperial) and should show:

 

a.         The locations of all major fixed elements within the leased premises dimensionally related to grid lines and demising partitions;

b.         Room names, numbers (if applicable), and uses;

c.                 The locations and layouts of rooms with unusual loading concentrations (for example, centralised filing areas, libraries), including a listing of loading conditions;

d.         Materials and finishes throughout the premises;

e.         The number of people to occupy the suite, including all heat load calculations for the determination of H.V.A.C. requirements (may need more info re ASHREA standards); and,

f.       Where the leased premises occupy less than a full floor, plans must be included of the entire floor showing the location of the leased premises and their relationship to the elevator lobby, exits, washrooms, etc. 

 

2.            Telephone and Power Outlet Plan

 

Drawing scale must be 1:100 (metric) or 1/8" = 1'-0" (imperial) with dimensions and locations of all telephone and power outlets.

 

3.            Reflected Ceiling/Lighting Plans

 

Floor plans should have a drawing scale of 1:100 (metric) or 1/8" = 1'-0" (imperial) and should show:

 

a.            Lighting, layout, ceiling pattern, air transfer ducts, materials and suspension-system details;

b.            The locations of any sound baffles above the ceiling;

c.            The locations of any access panels required to service building systems; and,

d.            The locations of any air transfer ducts through full height partition.  Cross talk silencers are required for all tenant and corridor demising walls.

 

4.            Sections and Details

 

Sections and details must be drawn to a suitable scale and shall indicate partition details, baffles, doors, etc.

 

5.            Room Finish, Door and Hardware Schedule

 

Two copies of the hardware schedule must be submitted to indicate all elements including keying, which must be to existing building standards.

           

6.            Complete Mechanical, Electrical, Sprinkler, Building Automation and Life-Safety System Drawings

 

Drawings must be scaled at 1:100 or 1/8" scale, showing all work that is an alteration/addition to the base building system and all parts of the base building system that remain unchanged.  Tie-ins and extensions to base building security, fire alarm, and communication systems must also be clearly shown.

 

7.            Structural Drawings

 

Structural drawings must only be supplied when modifications to the structure are anticipated.  These must be created by the Landlord's Structural Engineer or co-ordinated by the Landlord.  The Landlord’s contractor shall perform these structural modifications and will be co-ordinated by the Landlord at the Tenant's expense.

 

8.            Specifications

 

Project specifications must be submitted with the final set of working drawings describing the quality and performance standards for all of the Tenant work.

 

The Tenant is responsible for obtaining all necessary permits and approvals, from the Building Department, Health Department, Fire Marshall, the Ministry of Labour and any other governing authority having Jurisdiction.  The Tenant shall submit copies of the building permit and any other required permits or approvals with the Landlord, prior to the commencement of the Tenant's construction.

 

The Tenant shall engage, at the Tenant's expense, the Landlord's contractors, for any mechanical, electrical, sprinkler, controls and balancing modifications or additions to the base building systems.  The Landlord must be notified prior to any modifications to the base building systems.

 

Upon completing its review, the Landlord shall return the drawings stamped and endorsed with its approval along will all comments and required corrections of the Landlord and his Consultants.  The Tenant shall revise his drawings to include all the comments and corrections and provided the Landlord with a revised set of prints prior to commencing the Tenant work.  Unapproved drawings shall be revised to conform to the Landlord's requirements by the Tenant and resubmitted to the Landlord for approval before executing any work.  The Landlord shall not be obligated to change or extend any of the dates contained in the lease as a result of the drawings being rejected by the Landlord and/or its Consultants.

4.2.3        Following Approval of Tenant Drawings

 

1.            Documents required prior to commencement of construction

a.            Landlord written acceptance of Tenant drawings/specifications;

b.            Copies of Addenda (i.e. contract amendments);

c.            Copy of Building Permit;

d.            Worker's Compensation Board Clearance Certificate from general contractor and sub-trades;

e.            Certificates of Insurance in accordance with Lease documents;

f.              Two (2) sets of construction drawings and specifications plus one (1) set of electronic CAD files on CD;

g.            List indicating General and Subcontractor's contact names and telephone numbers for after hour emergency use;

h.            Project schedule, including construction meeting schedule; and,

i.               Letters of acknowledgement from Architects, Engineers (if different from Base Building Consultants), and the General Contractor stating they have read and will adhere to the Design Criteria Manual and its requirements.

2.            Documents During Construction

a.            Copies of all site-meeting minutes to the Construction Services Project Manager and Manager of Technical Services;

b.            Copies of all Contemplated Changes at time of issuance to Contractors;

c.            Copies of all Architect or Designer site visit reports; and,

d.            Copies of all site reports from authorities having jurisdiction.

3.            Documents following the Completion of Work

a.            Complete set of Consultant approved "As-Built" Drawings of the installation in AutoCAD 2000 or 2002 format.  Provide drawings in electronic format (CD-ROM);

b.            Letter from Tenant's Designer/professional consultant that the installation has been completed in accordance with the contract drawings and specifications and authorities having jurisdiction;

c.            Confirmation from Tenant that all surplus base building equipment/material that is to remain the property of the Landlord has been delivered to the Landlord in working order;

d.            Written verification that air balancing deficiencies have been identified and corrected; and,

e.            Letter from the City of Toronto confirming that the building permit is closed.

5.        TENANT CONTRACTOR(S) REQUIREMENTS

5.1              The Tenant is required to engage its own contractors for the purpose of carrying out its leasehold improvement work.  All Tenant Contractors are:

 

a.         Subject to approval by the Landlord;

 

b.         Must be in good standing with the Workplace Safety and Insurance Board (WSIB); and,

 

c.         Must utilize the base building automation, fire alarm/sprinkler and controls subcontractors for any leasehold improvements involving work from these trades.

 

5.2              The Tenant shall engage their Contractors to execute the Tenant leasehold improvements.

 

5.3              The Tenant Contractors are subject to the following conditions:

 

a.         The Landlord reserves the right to approve all construction work carried out by the Tenant's Contractors to ensure its compliance with approved drawings and building standards;

 

b.         Insurance: The Tenant and their Contractors shall, prior to commencement of  construction furnish evidence that they are adequately and properly covered by insurance, according to the following terms:

 

All Contractors and Subcontractors connected to any work within the Property are required to list the following on all Certificates of Insurance (insurance policies):

 

Certificate Holder:

GWL Realty Advisors Inc.

33 Yonge Street, Suite 418

Toronto, Ontario

M5E 1G4

 

Additional Insured (use same address):

London Life Insurance Company

1213763 Ontario Inc.

 

c.         A valid Comprehensive General Liability policy with a limit to any one occurrence of $5,000,000.00. The policy shall contain a cross liability clause and shall be extended to include non-owned automobiles and blanket contractual liability, in accordance with of the Lease;

 

d.         An "all risk" of physical loss or damage policy be provided covering the total contract price for the Tenant's work, in accordance with the Lease;

 

e.         An automobile policy be in force covering all owned vehicles, with a $2,000,000.00 combined single limit liability for bodily injury and property damage;

 

f.           All Policies of insurance relating to Tenant work must be in amounts and in form and with insurers acceptable to the Landlord, including an undertaking by the Insurers to give at least thirty (30) days written notice of cancellation or material changes to the policy holder and the Landlord;

 

g.         Evidence of the existence of insurance covered referred to in this section must be submitted to the Landlord by means of a Certificate of Insurance from the Tenant's or the Contractor's Insurers or by a certified copy of the actual policy documents before commencement of Tenant's construction; and,

 

h.         The Tenant and their contractor shall indemnify, defend and hold the Landlord harmless from all claims and hereby assumes all risk of damage to property or injury to persons in, upon or about the premises from any cause arising from the Tenant's construction.

 

i.            The Contractor is to complete a Tenant Work Permit Request Form, which can be obtained from the Tenant Services Coordinator at the Property Management Office.  A sample of the Form can be found at the end of this Manual.

 

j.            Must sign-in with Security at the beginning of every work day and receive approved Contractor Access Passes.

 

k.          Appropriate work attire must be worn at all times (i.e. company shirt, no ripped/torn clothing, presentable appearance, etc.).

 

5.4              Protection

 

The Tenant shall undertake to protect the Landlord and its interests against the placing of liens under the Construction Lien Act by the Tenant's contractors and suppliers, and to discharge forthwith at its own expense any liens registered against the building and lands which arise as a result of the Tenant's work.

 

5.5              Permits

 

Tenant's design and construction work must comply with all applicable By-Laws.  The Tenant must obtain all necessary permits and approvals from the appropriate government authorities before construction begins within the leased premises.

 

A copy of all permits must be delivered to the Landlord through the Tenant or by the Tenant’s representative.  The Tenant must correct immediately any work that does not meet with the approval of the building inspector, even though the Tenant's drawings may have been approved previously by the appropriate government authorities and the Landlord.  Any revisions to the approved drawings requested by such authorities must be brought to the attention of the Landlord immediately.  Should the Tenant unduly delay the required corrections, the Landlord may make the corrections at the Tenant's expense.  All permits must be closed with governing authorities upon completion of the work.  A copy of the closed permit(s) must be submitted to the Landlord.

 

A copy of the permit drawings must be made available at the Landlord's request.

           

5.6              Approved Drawings

 

A set of prints of the reviewed drawings must be kept on the leased premises for the duration of the construction period, so as to be available for reference purposes to the Landlord's authorized representatives.

 

5.7              Construction Schedule

 

The Tenant must provide the Landlord (prior to commencing construction activities) with a construction schedule outlining the start-up date, and completion date.  The Landlord will also require a complete list of the Tenant's Contractors and Sub-trades, which will be listed on a Contractor Access Form and registered with site security.

 

5.8              Existing Finishes

 

The Tenant’s Contractors must adequately protect all building finishes and carpets to prevent any damage.  Damage to building finishes caused by Tenant contractors will be repaired by the Landlord at the Tenant's expense.

 

5.9              Exposed Construction Premises

 

All work not contained within the demising walls and exposed to the public must be enclosed by full height, one side plywood boarding painted to match the Landlord's standard colour.

 

5.10          Tenant’s Contractor Access Requirements

 

All Tenant construction personnel must check in and out with site security at all times.

 

6.        COMMENCEMENT OF TENANT’S IMPROVEMENTS

6.1              The Tenant shall have obtained all necessary approvals and permits from all regulatory bodies having jurisdiction over Tenant's work and evidence of all such approvals and permits shall have been provided to the Landlord.

 

6.2              The Landlord in writing shall have approved the Tenant’s contractors and sub-contractors.

 

6.3              The Tenant shall have furnished proof of insurance.

 

6.4              Inspection of Tenant Premises

 

Prior to commencement of any Tenant work.  The Tenant, his agents, and the Landlord’s representative shall perform an inspection of the Tenant’s premises.

 

A signed letter shall be issued confirming acceptance of Tenant area and any damages or deficiencies shall be indicated at that time.  If any claims of deficiencies are made subsequent to the aforementioned inspection, and have not been documented prior to the commencement of work, the Tenant will be held responsible and shall correct said deficiencies to the Landlord’s satisfaction solely at the Tenant’s cost.

 

The Landlord shall issue written notice to the Tenant advising that all the conditions prerequisite to the commencement of Tenant work have been complied with to the satisfaction of the Landlord.  This notice shall be presented to the Tenant contractor before he will be permitted access to the premises to begin the Tenant work.

 

6.5              Inspection of Tenant's Work In Progress

 

The Landlord and its Agents, Architects, Engineers, and Consultants shall have unlimited access to the Tenant's premises for the purpose of inspecting the Tenant Work In Progress.  The Landlord or its Architects, Engineers or Consultants may note deficiencies in the Tenant work which shall be corrected by the Tenant immediately solely at the Tenant’s cost.

           

The Tenant’s Contractor may be issued revisions to the documents outlining regulations and procedures for Tenant Contractors and Subcontractors on the job site, from time to time as site conditions warrant.

 

After completion of Tenant work another inspection shall be of the premises between the Landlord’s representative and the Tenant, to be scheduled by the Tenant.

7.        SECURITY CONTROL

7.1              Keys (or Access Cards)

 

Access into the Tenant's leased premises should be agreed upon by and arranged between the contractor and its client.  Only designated contractor personnel will be issued common area keys.  These keys will be held at the Security Desk and must be signed out and in on a daily basis.  Re-keying costs for keys that are lost will be the responsibility of the Tenant.  These costs will vary depending on the particular key lost.

 

7.2              Working Hours

 

Generally accepted business hours of operation are from 8:00 a.m. to 6:00 p.m.  No work is to proceed in areas exposed to the public during normal business hours.

           

Construction materials for the premises shall be delivered prior to 8 a.m. or after 6:00 p.m. using only the service elevator, Monday to Friday.  Work within reasonable noise limits may be carried out during normal working hours; however, tenant complaints will not be tolerated.  If construction activity during business hours generates tenant complaints, the Landlord reserves the right to cease work immediately.  It is then the responsibility of the Tenant and/or Tenant’s Contractor to reschedule work outside of generally accepted business hours solely at the Tenant’s expense.  Any work which to be done at other times must be specifically agreed upon and arranged with the Landlord providing a minimum of 24-hours notice; weekends subject to availability.

 

For further clarification of construction activities which generate noise, please see Item Numbered 30 of this Section.

8.        PUBLIC SAFETY

8.1              It is the Tenant's responsibility to ensure that the Tenant contractor observes and complies with all applicable construction/safety guidelines and regulations. Any additional safety regulations imposed by an authorized representative of the Landlord must also be complied with, immediately and fully.  Should failure to comply result in any construction delay, the Tenant will be held responsible for all resulting costs.

 

8.2              The Tenant shall ensure that the Contractor and all Subcontractors observe and enforce all construction safety measures as contained in the requirements of any Federal/Provincial Legislature, regulations, Municipal By-Laws and requirements and the requirements of all other authorities having jurisdiction which may pertain to construction of the work.

 

8.3              In the event of any conflict between any Municipal By-Laws, Provincial or Federal Legislation, the provision that sets out the most onerous or stringent requirement shall apply.

 

8.4              The Tenant must ensure that its Contractor and Subcontractors:

 

a.         Comply with, but not limited to all ordinances, the requirements of all Acts and Regulations with respect to health and safety including Occupational Health and Safety Act, RSO 1980 Chapter 321 (as amended) and Regulations for Construction Projects (as amended) made there under; and Workplace Hazardous Material Information System (WHMIS) Regulation, Ontario Regulation 644/88;

 

b.         Before commencement of work and throughout Contract, maintain on site and readily accessible to all those who may be exposed to hazardous materials, a list of all hazardous materials proposed for use on Site or Workplace together with current Material Safety Data Sheets MSDS);

 

c.         Ensure hazardous materials used and/or supplies on site are labelled in accordance with WHMIS requirements;

 

d.         Provide detailed written procedures of safe handling, storage and use of such hazardous materials including special precautions, safe clean up and disposal procedures which conform to the Environmental Protection Act for disposal requirements;

 

e.         Ensure that those who handle and/or exposed to or are likely to handle or be exposed to, hazardous materials are fully instructed and trained in accordance with WHMIS requirements; and,

 

f.           Ensure that all chemicals and hazardous materials are disposed of according to the relevant standards, policies, and procedures.

9.        EMERGENCY CONTACT

9.1              The Tenant and its Contractors are required to provide the Landlord’s representative with the names and telephone numbers for contact in case of an emergency relating to the Tenant’s premises or any activities within.

10.   TEMPORARY SERVICES

10.1          Restrooms and Common Areas

 

Common areas and washrooms may be used by the Tenant's Contractor.  The Tenant’s Contractor is to coordinate additional cleaning requirements with the Landlord’s representative during the construction period.  Should the common areas be soiled by any trades using the facilities, the Tenant will be held completely responsible and billed for any cleaning services required plus the Landlord’s mark-up for administration and coordination.

 

 

 

 

10.2          Power

 

a.         The Tenant's contractor is responsible for the distribution of temporary power and telephone services within the leased premises during the construction period.

 

b.         The Tenant will be responsible for all cleaning and repairing any and all damages.

 

c.         Temporary power shall be made available by the Landlord in base building electrical/telephone rooms and shall be charged to the Tenant’s account on a pro-rata/square foot basis.

 

10.3          Telephone

 

The main telephone service to the building is through Bell Canada.  The Landlord must approve any other communication requirements in writing.

 

The Tenant and its Contractors requiring the use of a telephone must make arrangements to have telephone service installed within the premises.  The Tenant and its Contractors will not have access to the Landlord's telephone.

 

10.4          Heat

 

The Tenant's Contractors are to supply any necessary temporary heating units.  Hook up and disconnect to the building supply line will be done by the base building mechanical trade; the costs of which will be billed to the Tenant's account.  A consumption rate for recorded use will also be applicable to the Tenant's account.

 

10.5          Loading Dock and Deliveries

 

The loading dock for 33 Yonge Street is located off of Wellington Street. The facility is open for regular service from 6:00 A.M. to 6:00 P.M., Monday to Friday (Statutory and designated holidays excluded).  Dock regulations are clearly posted and shall be adhered to at all times.  Failure to do so may result in a revocation of privileges.  The Landlord and Property Management assume no responsibility for breakage, damage, theft or personal injury however so caused.

 

All deliveries of materials to the leased premises and construction site must be booked through the Landlord’s representative providing a minimum of 48 hours notice.  Large deliveries must be made before 8:00 A.M. or after 6:00 P.M., Monday to Friday or from 8:00 A.M. to 6:00 P.M. on weekends and/or Statutory Holidays, subject to availability.

 

 

 

 

10.6          Service Elevator

 

The service elevator is located directly adjacent to the loading dock facilities.  The elevator cannot be taken out of normal service between 8:00 A.M. and 6:00 P.M., Monday to Friday.  Elevator booking is on a first come, first serve basis and arrangements must be made providing 48 hours written notice to the Property Management Office.

 

Please note that under Section 3.9.2.2.1 of the CSA B44 94 Elevator Code, the weight of any single piece of freight or of any single hand truck and its load cannot be more than 25% of the rated load of the service elevator.  The rated load for the service elevator at 33 Yonge Street is 3,500 pounds; therefore, in order to comply with the respective code, no single load can exceed 875 pounds. For single piece loads exceeding 25% rated capacity, special arrangements may be made with the Elevator Contractor to be arranged by the Property Management Office.  Any costs incurred as a result will be solely at the Tenant's expense.

 

Personnel required to supervise on-site activities, and the cost of same, will be at the Tenant's expense.  Trades are not to utilize regular passenger elevators and are restricted to the use of the service elevator only during regular business hours.

 

10.7          Work Areas

 

All construction materials, tools, equipment and workbenches must be kept within the leased premises throughout the construction period.  All public lobbies, corridors, washrooms and stairs shall be kept clear of construction materials at all times.  Construction activities must respect any and all applicable Fire Safety Regulations.

 

10.8          Garbage

 

Corridors, exits, freight elevator lobbies and common areas must be kept clear at all times.  Removal of all construction garbage is the responsibility of the Tenant's contractor.  Arrangements must be made for elevator time to remove construction debris to the loading dock.  Due to space constraints, the Tenant or the Tenant’s Contractor must immediately remove debris from the site by whatever means possible at the Tenant’s expense.

 

For clarity, removal of Tenant's construction debris will be scheduled between the hours of 6:00 PM to 6:00 AM.  Bins will only be accepted on site during these hours.  Booking of the service elevator for transporting debris must be co-ordinated through the Property Management Office with a minimum of 48 hours notice.  The Tenant's Contractor is responsible for the most efficient use of the service elevator at the Landlord's discretion. A building representative may be required, at the discretion of Property Management, after hours and the cost which will be charged to the Tenant.

11.    TEMPORARY FIRE PROTECTION DEVICES

Operable fire extinguishers must be kept on the leased premises throughout the construction period and these extinguishers must be sufficient in number and of suitable type to combat a potential fire in the work area.  Any contractors working with an open flame must provide their own fire extinguishers in an operable condition.  Base building extinguishers are not to be removed from cabinets.  Approval from the Property Management Office must be obtained before any work of this nature is undertaken.

12.      SECURITY OF LEASED PREMISES

The Tenant is fully responsible for the physical security of the leased premises and the contents thereof throughout the construction period and occupancy.  The Tenant's Contractors(s) shall be restricted to the enclosed leased area for all work and storage of all construction materials, tools and equipment.

13.      FASTENINGS

Tenant Contractors are not permitted to mechanically fasten to window frames, fire-rated walls or exterior walls containing structural air/vapour barriers. Clips must be used to fasten interior partitions to the ceiling grid, screws are not permitted.

14.    PROTECTION OF BASE BUILDING ELEMENTS

14.1       Radiator enclosures shall not be used as a step or for storage of materials, etc. Repairs for damages shall be the responsibility of solely the Tenant.

 

14.2       Mechanical and Electrical Room

 

The Tenant shall be responsible for cleaning and making good any damages to the Mechanical and Electrical rooms.  In particular, floor drains shall not be used for dumping of liquid waste, etc. 

 

14.3       Ceiling Grid

 

Base building construction has erected the ceiling grid to typical floor ceilings.  The Tenant shall be solely responsible for any damages to this grid due to Tenant work.

 

14.4       Stairs and Access Areas

 

The Tenant is responsible for cleaning and making good any and all damages to stairs and other common areas used for access during Tenant work, and caused by the Contractors.  Tenant Contractors shall not wedge fire doors in stairwells open.  The Landlord at the Tenant’s expense shall repair any damages to any elevator cabs, doors or frames.

15.      ACCESS PANELS

Access panels in wall, ceiling and floor construction must be provided by the Tenant at their own expense and as directed by the Landlord to permit necessary access to equipment or services.  The Contractor is to co-ordinate on site the location, number of panels etc. with the Property Management Office.

16.      TIE-INS

The Tenant must obtain the Landlord's permission in writing before installing any tie-ins such as mechanical or fire protection or life/safety systems, and before testing any such tie-ins.  Where any tie-ins are made to existing services i.e., domestic water, sanitary, etc. provisions for future accessibility and isolation must be made, the costs of which are the sole responsibility of the Tenant or their Contractor.  At the sole expense of the Tenant, the Landlord's fire Safety Consultant shall be retained to verify any and all fire system alterations.  An addendum certificate must be provided to the Property Management Office.

17.      FIRE ALARM

17.1       Sprinkler System

 

All revisions to the base building sprinkler system must be approved by the Landlord or authorized personnel in writing.  The sprinkler control valve will be closed and the sprinkler line drained down each day until all Tenant revisions on each floor are completed.  All sprinkler systems components must be able to be made operable at the end of each day.  The Landlord must be contacted 48 hours in advance of any proposed sprinkler work, and before commencing work on the site.  All precautions must be taken to ensure false fire alarms do not take place. Charges will be levied against the Tenant's account (cost plus 15% administration fee), etc.  Sprinkler work requiring isolation of occupied areas must be completed during normal business hours (9:00 AM to 5:00 PM, Monday to Friday).  The Contractor must provide a fire watch person for occupied areas in accordance with the building fire plan at the Tenant’s sole expense.  Work outside of these hours must be scheduled with the Property Management Office.  Any work concerning the Standpipe must also be scheduled 48 hours in advance; to be done after 6:30pm and be completed before7:30am.

 

After completion of all Tenant work the system must be water pressure tested at 150 psi for two hours.  The Landlord's base building engineering consultant must witness the test and send the test certificate to the Property Management Office.  The sprinkler system will be reactivated once all tests have been approved.  The Tenant is responsible to ensure that the relocation or addition of heads conforms to all applicable N.F.P.A. standards, I.A.0. requirements, and to all authority requirements.

 

a.      A temporary smoke detection system must be installed in the event that the sprinkler system and building smoke detection system becomes inoperable at the end of each day; and,

 

b.      A full set of approved hydraulic calculations and drawings must be forwarded to the Property Management Office from the sprinkler contractor prior to any work commencement.

 

17.2       Fire Alarm and Devices

 

All work performed on the base-building fire alarm system shall be performed by the base-building fire alarm contractor unless otherwise approved by the Landlord.  All costs associated with this work shall be borne solely by the Tenant.

 

Arrangements must be made with the Property Management Office prior to performing any work on the fire alarm system.  Only building personnel are allowed to isolate the fire alarm panel when modifying, installing and/or relocating any alarm devices (i.e. pull stations, communication speakers. fire alarm bells, etc.).  Audible verifications to system must be between 12am and 7:30am.  The Tenant will be charged $500.00 per alarm should the Tenant's contractor inadvertently cause an alarm.  The Fire Alarm System must be in an operable condition at the end of each day before 5:00 P.M.

18.     LIGHTING CONTROL SYSTEM

33 Yonge Street employs a sophisticated, dimmable and individually addressable lighting control system throughout the building by the manufacturer Fifth Light Technologies.  This system controls most all light fixtures, but does not include pot lights, various common area lighting elements, or emergency light fixtures.

Whenever a Tenant chooses to carry out alterations to the existing lighting system, be it in layout or in quantity of light fixtures, a Base Building electrical contractor who is familiar with the system and its various requirements is to be utilized (Please see Section IV – Approved Contractors for a list of approved contractors and their corresponding contact information).

Should you require any clarification regarding the system, or more detailed information, we recommend the Tenant’s contractors contact Fifth Light Technologies directly (contact information found in Section IV – Approved Contractors).

Upon commencement of any construction related activities, it is the Tenant’s responsibility to ensure that the integrity of the system is maintained at all times (i.e. not damaged by construction activities).  Should the system cease to function correctly and require servicing as a result of any construction related activities; the Tenant will be invoiced for all work orders including an administration and coordination fee.

It is also the Tenant’s responsibility to commission any and all changes made to the lighting system, to ensure that the integrity of the system is maintained.  Any and all costs pertaining to the commissioning of the lighting system are solely the Tenant’s responsibility.  The commissioning process is to be handled by Fifth Light Technologies Inc (FLT).  FLT’s contact info can be found in Section IV – Approved Contractors.

 

19.   ELECTRICAL PANEL AND TENANT SUBMETERING SYSTEM

As part of the work to build-out a Tenant’s new premises, the Tenant is required to install, at their sole expense, separate electrical panel(s) for any electrical services supplied to said premises (unless stipulated otherwise). All newly installed electrical systems must be tied into the new electrical panel(s).  Additionally, all existing electrical systems within said premises are to be relocated to the newly installed panel.

Tenants are required to install; at their sole expense, Measurement Canada Approved Meter ManagerTM Electronic Submeters supplied by Carma Industries.

Electronic Submeters for electricity measurement are required for all tenant electrical services, including receptacle power, mechanical units, lighting and supplementary air conditioning units, etc, unless otherwise stipulated by Property Management.

20.   DRILLING OR CUTTING WORK

All hammer drilling must be done before 7:30 AM or after 6:00 PM.

The Tenant's Contractors may not drill or cut openings of any type in any part of the base building structure.  Where such work is deemed to be necessary, it must be approved in writing by the Landlord and the building’s Structural Engineer, carried out solely at the Tenant's expense.  X-raying of the structure is mandatory; 1 weeks notice is required.  All core locations shall be submitted in drawings, accompanied by the X-rays for review and approval by the Landlord’s representative a minimum of three (3) business days prior to proposed drilling.

21.   WELDING AND ANY OPEN FLAME WORK

Open flames for welding, cutting or other purposes are not permitted without the prior consent of the Landlord.  Proposed work of this nature must be approved by Base Building Operations in writing with at least 48 hours notice before the work is to be done.  An operational fire extinguisher must be available in the immediate vicinity of the work, in addition to those already present.  The Tenant Contractor shall co-ordinate shut off or covering of the smoke detectors with the Property Management Office.  Should the Tenant Contractor neglect to notify the Property Management Office regarding the above-noted work and a fire alarm is activated, resulting in a false alarm, the Tenant contractor will be charged with all associated costs plus a fine of $500.00 per occurrence plus an administration fee.

22.   WATER SYSTEM SHUTDOWNS

All requests for water system shutdowns (fire, line, domestic, water, etc.) must be submitted in writing for approval at least 48 hours before the shutdown date to the Property Management Office.

23.   CARPET INSTALLATION

Carpets may not be glued to the floor, except when a "quick-release" type of glue is used and the Landlord's approval has been obtained.  Installation of all carpet within the Tenant's premises must be completed after normal business hours.

24.   PLUMBING

Where plumbing is removed from Tenant premises, all water supply, drain lines and vent connections must be removed from the ceiling spaces back to the core riser and properly capped.  Installation of water meter(s) will be required on all incoming lines to the Tenant's premises servicing any kitchens, private washrooms and HVAC equipment.

25.   DAILY CLEAN-UP

Contractors must ensure that corridors are left free of debris and must remove dirt and marks from corridor walls, floors, doors, etc., on daily basis.  Where special cleaning is required to maintain the corridor's neat appearance, such cleaning will be done by the Landlord’s service provider solely at the Tenant's expense.

26.   COMPLETION OF WORK

26.1       At the completion of work, the Tenant must provide the Landlord with a complete set of "As-Built" sepia drawings.  An Ontario Hydro Certificate of Approval must also be submitted.

 

26.2       All elements of the base building, such as, but not limited to, light fixtures, ceiling tiles, doors and frames, hardware etc., that the Tenant removes with the approval of the Landlord remain the property of the Landlord, the delivery of which must be coordinated with the Property Management Office.

 

26.3       At the completion of construction the leased premises must be left clean and in a “move-in” condition.  The Landlord's cleaning contractor may be retained at the Tenant's sole expense to complete this work.

 

26.4       In addition to the foregoing obligations, Tenants are also responsible for ensuring, before premises are occupied or re-occupied, that the following areas and/or items are cleaned:

a.         Light fixtures and lenses;

b.         Ceiling and ceiling tiles;

c.         Floor tiles and carpets;

d.         Corridor walls and doors immediately adjacent to the leased premises;

e.         Perimeter radiation units (inside and outside);

f.           Lint screens and coil (cleaning shall be carried out by the Landlord's base building cleaners and charged to the Tenant's account);

g.         Interior side of all perimeter exterior windows and any partition glass installed within the leased premises;

h.         All service rooms;

i.            Venetian blind (excluding perimeter blind) cleaning shall be carried out by the base building cleaning company, and charged to the Tenant's account; and,

j.            The filters for the floor air-handling unit must be replaced following construction.

27.   STATUTORY DECLARATION FORM

The Tenant and its general contractor must complete and execute a Statutory Declaration Form protecting the Landlord against any and all liens, charges or claims for any work performed or material furnished.

28.   AIR BALANCING REPORT

The Tenant must coordinate through the Property Management Office, the Landlord's Air Balancing Contractor to provide an air balancing report upon completion of all leasehold improvement work including all expansions and new renovations.  The report must be done at the Tenant's expense and must be reviewed by the Landlord's consultant.  A complete floor fan system air balance must be performed as part of the retrofit scope of work for any partial or full floor occupancy.

29.   DAMAGE

29.1       Once a floor has been handed over to a Tenant's General Contractor, the Contractor is responsible for the entire premises.  All floor deficiencies will be confirmed in writing with mutual acceptance to be in perfect condition unless, prior to start of any work, an inspection by the Contractor and a Representative of the Landlord determines otherwise.

 

29.2       If during the construction period, should the Tenant's Contractor or Sub-Trades cause damage to the premises or public areas of the building, the Landlord, at its option, will carry out repairs at the Tenant's sole expense.

30.   CONSTRUCTION NOISE

Work such as coring and drilling MUST be carried out during non-business hours with the Landlord’s written approval in advance.  The Landlord reserves the right to cease any work that disrupts the surrounding Tenant’s right to quiet enjoyment.  Ceased work may be rescheduled at the Tenant’s (carrying out the work) sole expense.  Under no circumstances will the Landlord be held accountable for any cost increases incurred by the Tenant/Contractor for alternate scheduling of the associated work.

31.   SITE MEETINGS

The General Contractor is to arrange at regular intervals during construction, site meetings to include representatives of the Tenant, General Contractor, Sub-trades and Property Management, in order to deal with any problems, alter or arrange schedules and update work progress, etc.  It is also the General Contractor’s responsibility to record the Minutes of the Meeting and make them available to all parties.

32.   SPECIAL LANDLORD’S CHARGES PAYABLE BY TENANT

In cases of specialized construction or renovation where the Landlord provides special facilities, equipment or services, special charges may be levied.  The Property Management Office will inform the Tenant of such costs, whenever possible, before the costs are incurred.

33.   LANDLORD SUPERVISION FEES PAYABLE BY TENANT

The Property Management Office will assign a Landlord’s representative to liaise the Tenant Improvement Project.  This liaison will provide assistance/guidance with scheduling, coordination, approvals, etc.  Fees for the Landlord’s supervision of leasehold improvement work which shall range from $0.25 to $1.00 per square foot of leasable area (unless stipulated otherwise) depending upon the size and complexity of the project.  Charges at the time of this manual’s printing are subject to the contemplated lease agreements.

34.   AMENDMENTS TO LEASEHOLD IMPROVEMENT AREA

The foregoing information, procedures and regulations may be amended from time to time by the Landlord.  After receiving notification of such changes, Tenants must comply with any new requirements contained therein.

 

 

 

SECTION II

FINISHED, SYSTEMS, AND STANDARDS


1.        FINISHES

1.1              Ceilings

 

Finished ceilings are lay-in acoustic panels, in a t-bar suspension system, using a five-foot by five-foot (5'0" X 5'0") module.  The base building tile specification is Georgian 791C, 30" x 60" x 3/4" flame spread 25, smoke developed 10, fuel contributed 15.  All vacant space is fully equipped with installed tiles.  The contractor is responsible for supplying and replacing all tiles soiled or broken during construction.

 

1.2              Floors

Finished concrete floor slabs.

1.3              Core & Columns

 

Drywall prime painted base building standard white.

 

1.4              Curtain Walls

 

Fastening directly to the curtain wall is not permitted. (including mullions)

 

1.5              Radiation Units

All office furniture should be placed to allow a minimum of six inches (6”) clearance in order for the units to function correctly and enable access for maintenance.  Fastening to the radiation units is not permitted (including installation of power and telephone outlines).

1.6              Doors and Frames

 

Entrances to electrical rooms, janitor rooms, washrooms, stairways, etc. will be hollow metal doors in pressed steel frames, painted to base building standard.  Tenant entrances on multi-Tenant floors will be full height solid core wood doors with wood frames and will be finished on both sides with varnish, light oak veneer.

Exiting is to be in accordance with the Ontario Building Code. 

2.        MECHANICAL SYSTEMS

2.1              Heating, Ventilating and Air Conditioning Systems

 

The office floors of the building will be air conditioned by compartmental air volume units, one or two per floor according to the floor size.  Outside air will be provided to each compartment unit from a unit located in the roof penthouse.  Air will be distributed through ductwork to thermostatically controlled volume control boxes and introduced into the space through slot diffusers at the perimeter and lighting troffers in the interior zone.  Any addition or relocation of thermostats, VAV boxes, diffusers etc. deemed necessary to accommodate the Tenants floor plan shall be the responsibility of the Tenant. 

 

Air must move laterally through the office area to the core area fan rooms, return shafts and smoke shafts.  If partitions extend to the underside of the structure, openings must be provided for the free movement of air.  The office floors will be heated at the perimeter by hot water wall fin radiation in a continuous enclosure, thermostatically controlled (approximately 15 perimeter zones/56 interior per floor depending on floor plate size).  Perimeter thermostats will control both heating and cooling in sequence.  Closure strips shall be provided in the radiation enclosure at every window mullion.  The Tenant shall not directly utilize the base building exhaust system to accommodate any special room use i.e., smoking room.

 

The design criteria for office space are as follows:

a.            In winter 22oC (72oF) with 25% relative humidity at outside conditions of minus 20.5oC (-5o)F

b.            In summer 240C (750F) with 50% relative humidity at outside conditions of 320C (900F) dry bulb and 24.50C (760F) wet bulb temperature.

c.            Ventilation rate (outside air capacity) will be 0.15 cfm per square foot of occupied area.  (20 cfm per person with one person per 150 square feet).

d.            The Tenant's engineers will be supplied with information about air supply quantities which the Tenant design shall not exceed.

2.2              New Equipment Installation

Should a Tenant require supplemental cooling continuously i.e. computer room, an independent system should be installed at the Tenant's sole expense subject to the written approval of the Landlord.  Electrical and water meters are required to be installed at the Tenant's expense.

2.3              Plumbing and Drainage

Plumbing into the main domestic cold water supply and connections to the sanitary drain and vent risers are provided at the core to allow for the addition of a limited number of facilities in the leased premises, subject to the Landlord's approval.  Tenants requiring hot water must provide their own hot water tanks and water meters must be installed for consumption charges.

2.4              Fire Protection

On each floor a sprinkler system is provided.  In addition, fire hose cabinets, portable fire extinguishers, smoke detectors and annunciation speakers are base building standards.

Smoke exhaust systems for the Atrium and the office and retail areas have been specially designed to protect the open concept of the Atrium.  The system also functions if the openings to the Atrium are glazed.  If a fire occurs all smoke would be contained on the fire floor by creating a positive air pressure in the Atrium, stairwells and on other floors.  Smoke is exhausted by special smoke shafts in each quadrant of a floor.  This smoke control system is connected to a standby generator to ensure operation in all circumstances.  The smoke control system is also connected to the fire detection and alarm system.

In the event of a fire all elevators automatically return to the ground level.  The service elevator will be used for emergency use.  A voice paging system covers all areas of the building.  Emergency telephones are located in all stairwells.

3.        ELECTRICAL SYSTEMS

3.1              Lighting

The base building lighting system is provided by means of modular fluorescent coffered fixtures (100 watts/50 sq. ft.), controlled by Fifth Light Technology’s dimming ballasts. Standard office lighting levels are of 50 dekalux.  Lighting power is provided at 120 volts.  The introduction of incandescent lighting (pot lights, spotlights, etc.) adds greatly to both electrical and air-conditioning loading.  The base building design system adequately supplies 2.0 watts per square feet for Tenant use.  All electrical fixtures must be secured by a safety chain.

The installation of an OSC Intelimeter (9524572057), to meter all lighting in the Tenant’s leased premises, may be required by the Landlord, at the Tenant’s expense.

Master low-voltage light switches are required to be installed to control all lighting within the leased premises.  An inventory of light fixtures is available for additional requirements.  The cost of supplying additional fixtures will come at the Tenant's expense.

3.2.            Power and Telephone

Power for duplex outlets at 120/208 volts is available on each floor at a design capacity of 2 watts per square foot of rentable space.  Supply and installation and connection of outlets are the responsibility of the Tenant.  Requests for additional power requirements per floor will be reviewed by the Landlord.

An OSC Intelimeter model number 9524572057 may need to be installed to meter all power in the Tenant's leased premises.  Any deviation from the base building standard meter will require the Landlord's approval.

 

The telephone and electrical rooms, which are provided on each floor, are intended only for base communications and electrical services and are not accessible to the Tenant.  Any space of this nature which the Tenant requires for its own equipment or use must be provided within the leased premises.  Arrangements for telephone and communications services shall be carried out by the Tenant directly with the system supplier.  Under no condition shall these rooms be used for storage of materials.  Fire proofing through floor slab openings is required and shall conform to building standard detail.

All wiring in the ceiling (e.g. telephone and data communication lines) must be completely enclosed in conduit or it must be fire rated plenum cable.

3.3              Emergency Power

Building essential services are connected to an emergency power generator system. Each floor has a minimum coverage of emergency lighting.  The Tenant must connect to this system and may install additional emergency lighting, with prior approval from the Landlord.

4.        STRUCTURAL SYSTEMS

A general description of the structure is provided to the Tenant by means of copies of selected working drawings. Such additional drawings or information as the Tenant may reasonably require may be obtained from the Property Management Office.  Office floors have been generally designed to handle 100 pounds per square foot live load.  Unusually heavy loading situations, such as central filing areas, storage areas, vaults, safes, etc., must be specifically indicated, and details of projected floor loading supplied as part of the working drawings the Tenant submits to the Landlord.  Plans for such unusual situations are subject to the Landlord's prior approval and structural engineer's review.

5.        STANDARDS

5.1              Door Hardware

 

All door locks installed by the Tenant, on both entrance and interior doors, must be keyed to the building master and sub-master keying system using building standard door hardware.  The system allows complete freedom to the Tenant with respect to locking arrangements for its offices, while providing access to each office at all times for both normal cleaning and emergency situations.

 

The Landlord's locksmith, Action Locksmith, can be reach at (416) 261-1422 which maintains the master keying system and the records on key coding and distribution. Outside locksmiths or lock manufacturers are not permitted to change the keying of any locks. The Landlord's locksmith at the Tenant's expense must be engaged for the final keying.

 

It is advisable that the Tenant contact the Property Management Office before purchasing a hardware system to ensure that it is compatible with the base building system, Corbin Cl Pin.

 

5.2              Security Card Access Systems

 

The Property Management Office must be notified before the installation of any card-access system.  Any Tenant door equipped with a card reader must have a building master key override.

 

The base building security card access system (Intercon's ISL 8000) may be utilized by the Tenant for any or all entrance and interior doors.  The Tenant will be responsible to obtain any required permits and licenses from government authorities having Jurisdiction and for the installation of any required additional life safety devices (i.e. pull stations).

In the event that magnetic locking devices are to be installed, each must be tied into the master key override switch located in the Fire Control Room and to ensure all locks have been verified.

All costs associated with the installation will be at the Tenant's expense and at the sole discretion of Property Management Office; a nominal administration fee for card programming and reports requested may be applicable.  Please contact the Property Management Office for further information.

5.3              Venetian Blinds

            All windows are provided with horizontal venetian blinds, which may not be removed. 

5.4              Signage

Tenant identification signs in ground floor lobby directories, elevator lobbies and on the Tenant entrance doors must be in accordance with the Landlord's design criteria for such items as style, location and size.  Please note that no signs will be permitted to be installed on any corridor demising walls or atrium windows whatsoever.  The cost of all signs will be at the Tenant's expense.

All requests for signs must be submitted in writing to the Property Management Office indicating the exact wording and spelling required.  Requests should be submitted approximately two (2) months prior to the actual move-in date.


SECTION III

TENANT AND CONTRACTOR RESPONSIBILITY


1.        MECHANICAL

1.1              Labour, Materials & Fees

 

a.         Provide all labour and new materials for the complete installation of the systems.  Ensure that complete installation meets with the approval of all authorities having jurisdiction in accordance with all codes, etc.

 

b.         Arrange and pay for all permits and fees required for this installation.

 

c.         Use materials that are C.S.A., U.L.C., code approved, and C.G.A. or Ontario Hydro certified for the intended application.

 

d.         Comply with the intent of the base building specifications.

 

e.         Comply with the requirements as outlined in the Landlord's "Design Criteria Manual".

 

1.2              Examine the Site

 

a.         Examine the site and be familiar with all the conditions covered by these specifications.  Extras will not be allowed for failure to properly evaluate conditions.

 

b.         Take field dimensions prior to any installation.

 

1.3              Compliance With Codes

Comply with all latest relevant codes and local regulations having jurisdiction including O.B.C., N.B.C., N.F.P.A. 13, C.G.A. 149.1, C.S.A., O.W.R.A. 675/85, Canadian Plumbing Code, and Ontario Hydro Codes.

1.4              Debris & Clean Up

Keep premises clean as work progresses, avoid accumulation of debris, ensure that during construction all open vents are sealed and any controls (thermostats etc.) are covered.  On completion of the work, clean up and remove from site all scrap materials resulting from the work.  Clean all equipment prior to final inspection.

1.5              Co-ordination & Co-operation

Co-ordinate the work with all trades to ensure work may progress without delay.  Arrange the schedule of all work in co-operation with the General Contractor.

Co-ordinate the work with all trades and co-operate to ensure services do not conflict with the other services and / or structure.

 

Make allowances for such items as offsets to accommodate actual field conditions.  Refer to structural and architectural drawings (or site visit) for further building information.

Mechanical contractor shall indicate in red ink on an extra set of white prints all changes and deviations from locations on plans as job progresses.  On completion of the work provide the landlord with two sets of completed drawings showing location of all equipment, piping, ducting etc.

1.6              Warranty

Guarantee all work, equipment and materials for one year from substantial completion of the contract (A/C unit compressors - 5 years).

Ensure that all equipment is properly guaranteed by the manufacturer.

1.7              Shop Drawings

Submit shop drawings of all fixtures and equipment (including wiring diagrams) to the Landlord for approval.  Approval of shop drawings is gratuitous and does not relieve the contractor of his responsibilities.

1.8              Cutting and Patching

Provide cutting and patching for work.  Arrange to provide for the making good to finishes and include for the cost of this work.

1.9              Wiring

All power wiring:          Electrical Specifications

24 volt wiring only:       Electrical Specifications

Include for all necessary starters, disconnects, transformers and relays etc.

Ensure co-ordination between trades to avoid gaps and overlaps and to ensure all equipment is operational.

1.10          Demonstration

Allow for demonstration of all equipment to the Landlord and the Landlord's operating staff.

1.11          Miscellaneous

Provide structural steel support members as necessary to hang equipment, fans, ductwork, and piping from the building structure.  Paint all miscellaneous bare metal one coat grey oxide primer.

1.12          Alternatives

Assume full responsibility that the equipment offered as an alternative is suitable for the space allocated, and for any additional costs to any part of the work resulting from the use of an alternate.

No deviation from plans and specifications will be allowed unless written approval and consent is first obtained from the Landlord.

1.13          Maintenance & Operating  Instructions

Provide two copies of manufacturers’ maintenance and operating instructions for all equipment.

Present the instruction in indexed three ring hard cover binders, with spine label project indicator, and index sheet.  Including all shop drawings, permits, warranty details, certificates, contractor names, and telephone number lists for all project trades in this manual.

1.14     Interruption of Services

Any interruptions of the base building systems shall be co-ordinated with the Landlord for the time and duration and shall strictly adhere to the Landlord's instructions in this regard.

Include cost of premium time in tender price for the work outside normal working hours to maintain all mechanical services in operation without disruption to existing tenants.

1.15     Workmanship

Employ a responsible foreman to supervise the work and retain for duration of construction period.

Employ only skilled plumbers, steam fitters, sheet metal workers for the execution of the work.  Workmanship shall be first class as regards to durability, efficiency, safety, and neatness of detail.

 

2.        PLUMBING:

2.1              Piping Materials

 

a.            Condensate drain piping:           Type 'M' copper.

 

b.            Heat pump supply and return piping:

Steel pipe 50mm and smaller - schedule 40 electric weld or seamless ASTM specification A-53, 65mm and larger - schedule 40 as above ASTM specification A-53 with butt welding ends.  With steel pipe fittings up to and including 50 mm shall be threaded joints malleable iron, 65mm and larger shall be forged steel butt weld.

 

c.            Copper pipe 50mm and smaller type 'L' hard drawn copper with wrought copper solder type fittings.

 

d.            All elbows shall be long radius type.

 

e.            Victaulic and Gustin-Bacon systems are acceptable equals.

 

f.              Gate valves up to 50mm:

 

Crane 428

Jenking 810

RW/Toyo 293

Newman

Hattersley T605.

 

g.            Globe Valves up to 50mm:

 

Crane 7

Jenking 1068

RW/Toyo 221

Newman

Hattersley 13.

 

h.            Ball valves up to 50mm:

 

Crane 915

Jenking 33

RW/Toyo 5044A

Watts

B6000

Newman

Hattersley 1969AT.

 

i.               Flow balancing valves:               Armstrong CBV.

 

j.               Domestic water piping:

 

Type 'L' copper.  Exposed piping in finished areas shall be chrome plated.

 

k.             Drain and vent lines:

 

Cast iron with mech. joints, copper DWV or aluminum DWV pipe with cast iron fittings.

 

l.               Condensate drain piping:           Type 'M' copper.

 

m.          Domestic water valves:

 

Crane 438 and 1320

Jenking 310 and 313

RW/TOYO 280A and 281A.

 

n.            Shock absorbers:

 

Ancon shok-gard

Enpoco - HT series

Zurn - Shok Trol.

 

o.            When using solder on portable water piping, use 0.2% maximum lead solder or alternatively use 90/5/5 (tin/silver/antimony) lead free solder.

 

2.2              Piping Supports

 

a.         Support all piping using Clevis type hangers and riser clamps.  Use hangers of the same material as pipe, or insulating inserts between hanger and pipe.  Grinnell, Myatt, Economec or equivalent.

 

b.         Provide pipe covering protection saddle at each hanger where pipes are insulated.

 

2.3              Escutcheon Plates

 

            Provide escutcheon plates at all walls where pipes are exposed to view.

 

2.4              Unions

 

Provide unions to connect all piping to equipment to facilitate ease of maintenance.

 

 

2.5              Pipe Insulation:

 

a.         Insulate all domestic cold water piping and horizontal condensate drain lines with 1" thick fibreglass heavy density pipe insulation with all service jacket (ASJ).  Adhere a factory applied vapour barrier jacket lap smoothly and securely at the longitudinal seams with vapour barrier adhesive.  Adhere 3" butt joint strips over all end joints to ensure a continuous vapour barrier.

 

b.         Insulate domestic hot water piping with 1" thick fibreglass heavy density pipe insulation with full service jacket.

 

c.         Finish all exposed insulation with 6 oz fire retarding canvas.

 

d.         Clearly label pipe contents on pipe surface (i.e. D.H.W. or D.C.W.) and identify flow direction.

 

e.         Piping shall be concealed in finished areas and grouped so that valves etc. are accessible through as few access panels as possible.

 

f.           Run piping parallel to building lines with crossing over kept to a minimum.

 

g.         Identify all visible piping fully exposed or in accessible spaces (i.e. lay-in ceilings) with legend lettering (see below), direction of flow and field colour band.

 

                                                                       

Legend & Flow                      Field Colour

Medium                                 Legend                        Arrow Colour                         Band

 

Heat Pump Water Supply       H.P.W.S.                                 Black                           Light Green

Heat Pump Water Return       H.P.W.R.                                 Black                           Light Green

Condensate                            Cond.                                      Black                           Black

Cold Water                              C.W.                                        Black                           Light Blue

Domestic Hot Water               D.H.W.                                  Black                           Dark Blue

Sanitary Sewer                       San.                                         White                           Black

Plumbing Vent Line                 Vent                                         Black                           Black

Radiation Heat Supply            HWS                                       White                           Purple

Radiant Heat Return             HWR                                       White                           Purple

Condenser Water Supply       CWS                                       White                           Dark Green

Condenser Water Return       CWR                                       White                           Dark Green

 

2.6              Valve Tagging

 

a.         All valves shall have securely affixed to them a brass plate tag with embossed black numbers.

 

b.         Prepare for the Landlord a list of valve numbers indicating location and function.

 

2.7              Access Doors

 

Provide approved access doors to all valves, and etc.

 

2.8              Liquid Heat Transfer

 

a.         Provide heat pumps as noted on drawings.

 

b.         Refer to original base building specification for maintenance, flushing, installation, etc., on heat pumps.

 

2.9              Drains

 

a.         Provide Enpoco E-1000-R5-CI-PB-TSP floor drains where shown.

 

b.         All interior floor drains shall be piped and connected to trap seal primers TSP-2.

 

2.10          Cleanouts

 

Install all floor cleanouts with standard TY branch or Y branch and blend using Enpoco 3000-CI cleanouts with cover to suit floor finish.

 

2.11          Plumbing Alternatives

 

Enpoco numbers used in drains and cleanouts.  Equivalent alternates by Zurn, Ancon or Rototech Smith are acceptable.

 

2.12          Plumbing Vents

 

Plumbing vents are not necessarily shown on drawings.  However, install vent system in accordance with O.W.R.A. 675/85.

3.        H.V.A.C.

3.1              Ductwork

 

a.         Provide ductwork as indicated on drawings.

 

b.         Provide all ductwork to "SMACNA" standards.  Fabricate all ductwork from galvanised steel to the clear inside dimensions as noted on the drawings, with all flat surfaces cross broken.

 

c.         Install all ducts free from leaks and seal all holes with 3M #474 tape

 

d.         Duct thickness as follows:

 

Maximum Size

Gauge

Up to 12"        

26

13" to 30"        

24

31" and Over  

22

           

e.         Where any construction impediment or requirement renders the dimensions impossible, alter ductwork so as to give an effective cross sectional area equal to that originally shown without exceeding an aspect ratio of 4:1.  Make changes at no additional cost to the owners.

 

f.           Use bends where possible.  Use square elbows c/w turning vanes wherever bends are impractical.  Duro Dyne "Durovane Rail" or Hart & Cooley "Ducturn" or equal.

 

g.         Brace ducts so they do not vibrate or sag.  Support horizontal ducts up to 20" wide with 1" x14 ga. galvanised straps passing under ducts, on 8'0" centres.  Use angle iron support for ducts over 20" wide or deep.

 

a.         Provide approved access doors to all balancing and fire dampers, and etc.

 

h.         Supply and install splitter dampers at all supply air branch take-offs.  Dur-Dyne SRP or equal hardware.

 

b.         Paint inside ductwork black where visible through grilles, etc.

 

i.            Flexible ducting to be class 1 air duct connectors as listed and labelled by Underwriter's Laboratories of Canada, with flame spread of not more than 25 and smoke development classification of not more than 50.

 

j.            All round duct through 24" diameter shall be United Sheet Metal spiral lock-seam Uni-seal duct manufactured from galvanised steel meeting ASTM A-527-71 in the following gauges:

 

Diameter       

Metal Thickness

3" -   8"

28 Ga.

9" - 14"

28 Ga.

15" - 24"

26 Ga.

 

k.          All fittings shall be United Sheet Metal standard, or equal, uniform fittings manufactured from galvanised steel meeting ASTM A-527-71 with continuous weld or standing seam construction in the following gauges:

 

 

 

 

Diameter       

Metal Thickness

3" -   8"

24 Ga.

9" - 14"

24 Ga.

15" - 24"

22 Ga.

 

3.2              Duct Insulation

 

a.         Insulate ductwork with 1" thick internal neoprene coated fibreglass duct liner where indicated.  Adhere with min 50 % covering of fire retarding adhesive and supplement with welding pins.

 

b.         Make provisions for duct liner so that sizes shown on drawings are clear inside dimensions inside the insulation.

 

3.3              Fire Dampers

 

a.         Provide Ruskin or controlled air ULC rated Type B fire dampers.

 

b.         Install in accordance with N.F.P.A. 90A rated to suit fire rating of membrane to be protected.

 

3.4              Fans

 

a.         Provide fans as scheduled on the drawings.

 

b.         Adjust fans and motors to operate quietly, and make dampers tight to prevent vibration.

 

c.         Provide fans with spring isolation to give a minimum 95% efficiency.

 

d.         Provide flexible connections at each fan 24 oz. per yard tensile strength of not less than 500 lbs. with metal to 3" fabric to metal "Grip-Loc" duct connections.

 

3.5              Balancing

 

a.         Engage the service of the Landlord’s balancing contractor to balance and test all air handling systems under this section.

 

b.         This contractor shall:

 

                                    i.         Review drawings, specifications, and installed work to ensure that systems may be properly balanced in accordance with drawings.  Advise installing contractor of any additional requirements for effective balancing.

 

                                  ii.         Ensure that air handling systems are free from obstructions, that dampers are positioned correctly, that moving equipment is lubricated in accordance with manufacturer's recommendations, and that filters are clean.

 

                                 iii.         Demonstrate that the air handling system's performance is as specified and adjust variable speed pulley's and volume control dampers where necessary.  Each diffuser and grille shall supply or exhaust specified quantity with +/-5%.

 

                                iv.         Tabulate and certify test results on suitable forms and submit to the Landlord for approval record.

 

                                  v.         Perform this work in accordance with procedures and standards described in SMACNA "Balancing and Adjusting Manual".

 

3.6              Control Dampers

 

a.         Dampers shall be opposed or parallel blade low leakage type.

 

b.         Frames to be reinforced extruded aluminum with vinyl jamb and blade seals. Blades to be 6" maximum on centres. Damper actuators shall be oil submerged, spring return, two position 120/1/60 electric type. Bearings to be non-corrosive nylon.

 

c.         Damper seal shall be designed for minimum air leakage by means of overlapping seals.

 

d.         Dampers to be Nailor Hart, Ruskin or approved equal.

 

3.7              Variable (Constant) Air Volume Valves (V.A.V.)

 

Refer to schedules for type, capacity and size of variable volume air valves. Install in locations shown on plans.  All controls to match existing valves (Siemens).

 

3.8              Controls

 

a.         Provide for new and relocation of existing control components as indicated on drawings.

 

b.         Controls are to be supplied by "Siemens” or match existing and installed by the base building contractor.  However, heatpump thermostats are to be Climate Master Model # AT0907.

 

3.9              Control Air Tubing

            Minimum Requirements:

a.         Copper Tubing:

 

Hard drawn seamless type.

 

b.         Polyethylene tubing and polyethylene jacketed tubing bundles.

 

                                    i.         Maximum operating pressure:  80 p.s.i. at 140oF.

                                  ii.         Ambient Operating Temperature Range is 100oF to 175oF

                                 iii.         Number coded tubing in polyethylene jacketed tubing bundles.

 

                                iv.         "FR" stamped along entire length of tubing.

 

c.         Conceal tubing whenever in public areas, run parallel to building lines wherever exposed in mechanical rooms.

 

d.         Install tubing using standard connectors and adapter fittings.

 

 

e.         Install tubing with the building insulation between it and the outer building surface so that the tubing is isolated from the outdoor air temperature.

 

f.           Support tubing at regular intervals.

4.        ELECTRICAL

4.1              General

 

a.         All work shall be in accordance with the latest edition of the Ontario Hydro Code, Local Inspection, Ontario Building Code, and any other ordinance.

 

b.         Examine the site and all drawings and specifications of all trades and be familiar with the work of this trade.  No allowances will be made for the failure to do so.

 

c.         All electrical work shall comply with C.S.A. electrical bulletins applicable to tender close.  Where specific bulletins are not named they are still considered an integral part of this specification.

 

d.         Grounding shall be in accordance with the requirements of the Ontario Electrical Code.  Provide all grounding required regardless if not shown on the drawings.

 

e.         Provide all new materials having C.S.A. approval.  All workmanship shall be first class in regard to standard practices, safety, accessibility, durability and neatness of detail for acceptance by the Landlord's representative.

 

f.           Arrange and pay for all permits and inspection fees required for the work of this trade.  It is the responsibility of this contractor to submit to the Electrical Inspection Department and/or supply authority any and all drawings and specifications required for permits, fees, approvals, examinations and services.

 

g.         Provide all cutting and patching required for the work of this trade. All shop painted equipment damaged in transit shall be touched-up to match existing finish.

 

h.         Avoid accumulation of debris as the work progresses. On completion of the work, clean up and remove from the site all scrap materials resulting from the work of this trade.

 

i.            Co-ordinate the work of this trade with all other trades on the job so that the work may progress without delay.

 

j.            Prior to final inspection, clean all electrical equipment. Clean all construction dust and dirt from installed equipment at the conclusion of the job.

 

k.          Upon completion of the work, provide the final unconditional certificate of acceptance from Ontario Hydro Inspection Department to the Landlord.

 

l.            Provide a one year guarantee on all materials, and labour from the date of acceptance by the owner.

 

m.       The Electrical Contractor shall adjust phase loading, such as not to exceed a 10% phase imbalance.

 

n.         The electrical contractor shall submit shop drawings for power distribution equipment, fire alarm equipment, and all luminaries with associated equipment, i.e. poles, brackets etc. to the Landlord.

 

o.         The shop drawings shall bear the name of the manufacturer, the manufacturer's catalogue number, and the engineer's designation, along with all pertinent information on each piece of equipment.

 

p.         All equipment shall be mounted, plumed true.

 

q.         The electrical contractor shall obtain one set of blueprints, for 'as built' purposes, and make all necessary revisions on these blueprints to reflect actual on-site changes.

 

r.           At the end of construction, prior to final inspection by the engineer, the electrical contractor shall submit the as built drawings for review. Final inspection will not be carried out until these drawings are submitted.

 

s.         The base building specifications shall form an integral part of this specification and shall be strictly adhered to.

 

t.           The interior design drawings are to be consulted for all locations of devices and mounting instructions. Where device styles, colour, or orientation are specified on the interior design drawings these shall be strictly followed. Where requests by the designer are in conflict with the applicable codes, the Landlord's engineer shall be contacted for a decision.

 

u.         The Tenants electrical contractor shall be responsible for the installation and certification of any metered service. The fees and deposits for such metered service shall be the sole responsibility of the Tenant / Contractor.

 

4.2              Conduits and Raceways

 

a.         Use TWH or R90 copper conductors C.S.A. approved for the application.  Size conductors so that maximum branch circuit voltage drop does not exceed 3%.  Minimum conductor size is #12 AWG unless otherwise indicated.

 

b.         Design is based on copper conductors except where shown on the drawings, aluminum conductors may be used only for feeders 1/0 AWG or larger.  Size the aluminum conductors to the equivalent capacity of copper conductors.  Conductors in underground raceways may be RWU90 in poly pipe.

 

c.         Terminate aluminum feeder conductors with pressure connectors, and utilise an oxide preventative solution "Penetrox" on all bare surfaces. Lugs to be aluminum or aluminum/copper alloy only.

 

d.         All conductors are to be installed in raceways as described below;

 

                                    i.         Interior exposed surface raceways, branch circuit wiring from panel, concealed in accessible ceilings and walls or in concrete block construction: E.M.T. Raceways.

 

                                  ii.         In metal stud partition walls, branch circuit wiring from panels in suite or tenant occupancies, in concrete block walls for final drops and for final drops to fixtures in ceiling spaces (Length not to exceed 3 M in this application); Armoured Cable (Bx).

 

                                 iii.         All conduit and wiring is to be concealed in all finished areas.

 

                                iv.         Minimum raceway size for telephone and communication conductors is 19 mm (3/4 ").

 

5.        DEVICES

5.1              Switches

 

a.         Specification grade rated 15A, 125VAC, single pole, single throw (3-way or     4-way as noted on drawings).

 

b.         Spec grade, rated 15A, 240VAC, single pole single throw (3-way or 4-way as noted on drawings).

 

c.         Manufacturers: Smith & Stone, Harvey Hubbell, Leviton, Pass & Seymour, Eagle or equal 4.

 

5.2              Receptacles

 

a.         Spec grade, duplex, rated 15A, 125VAC, EEMAC 5-15R configuration, U-ground.

 

b.         Isolated ground, duplex, rated 15A, 125VAC, EEMAC 5-15R configuration, insulated, isolated U-ground.

 

c.         Ground fault interrupting Class A duplex, rated 15A, 125VAC, EEMAC 5-15R configuration, trip at 4-6 MA fault current. C/W push to test and reset buttons.

 

5.3              Cover Plates

 

Smoothline bakelite, colour to match switches and receptacles. Coverplates to be of the same manufacturer as the devices.

 

5.4              Dimmers

 

a.         Lutron Nova "T" Series. Wattage as indicated. Provide appropriate wall boxes for corresponding dimmer size. Do not gang dimmers in one outlet box.

 

b.         Manufacturers: Smith & Stone, Levito, Ideal, Prescolite or equal.

 

5.5              Equipment isolating disconnects

 

a.         Disconnecting devices to be sized for the current carrying capacities of the equipment to be isolated.  Provide number of poles as required by the equipment to be isolated.  Type of enclosure as indicated below:

 

                                    i.         Dust free or standard - EEMAC Type 1.

 

                                  ii.         Outdoor or damp location -EEMAC Type 3R.

 

                                 iii.         For direct exposure to water under pressure - EEMAC Type 4.

 

                                iv.         For high dust concentration of non-ignitable dust - EEMAC Type

b.         Manufacturers: Commander, Arrow-Hart, Scepter, F.P.L. Square D, Westinghouse, or equal.

c.         All devices of the same type, size and rating are to be of the same manufacturer throughout the project.

5.6              Service and Distribution

 

a.         Acceptable manufacturers for the distribution equipment include:

 

                                    i.         Commander, Federal Pioneer Limited, ITE (Seimens), Square D, Westinghouse.

 

b.         Label all disconnect switches, starters, and panels to clearly indicated equipment controlled or area serviced.  Indicate fuse size and type on all fused disconnects.

 

c.         Provide circuit breaker panels of the type, with ampere capacity, number of poles, branch breaker capacity etc., as specified in panel schedule.  Mounting to be as indicated.

 

d.         Provide a typed directory card on the inside of the panel door in a metal frame with clear plastic cover.

 

e.         All branch breakers shall be thermal-magnetic trip indicated, ambient temperature compensated and bolted to the bus-bar.

 

f.           All surface mounted equipment shall be mounted on 19 mm (3/4") plywood backboard.

 

5.7              Lighting

All primary standard base building office lights must be controllable by Fifth Light Technology’s dimmable ballasts.  Where atypical fixtures are installed (i.e. pot-lights, valence lights, etc.), provide fixtures complete with all accessories and mounting hardware, and lamps as approved by the Landlord. Acceptable products are manufactured by Sylvannia, York, Peerless, Prescolite, Halo, C & M, Capri, and Midday.

            Extra base building fixtures are available from the Landlord.

5.8              Emergency Power

 

a.         An emergency lighting circuit at 347V, 15A, is provided by the Landlord to receptacles located in the ceiling space. Receptacles are identified as emergency power.

 

b.         Emergency fixtures are direct wired to the emergency circuit.

 

c.         Emergency lighting circuit is fed from and emergency generator. When the generator engages it has a starting time of approximately 8 to 13 seconds.

 

d.         Exit Fixtures

 

                                 i.            Provide exit fixtures to match base building exit fixtures style and voltage, each fixture is to be LED illuminated (15T6 retrofit kit). Acceptable manufacturers are Emergi-Lite or alternates.  Extend base building exit fixture circuit from existing exit locations to new locations. 

 

                               ii.            Exit fixture circuit is connected to the building emergency distribution system.

 

5.9              Fire Alarm System

 

a.         The building fire alarm system is existing and operating. Before performing any changes to the system, alert the Landlord 24 hours in advance to allow the zone to be isolated.

 

b.         All devices which are disconnected and reconnected to the fire alarm system are to be verified for the operation prior to final inspection. Verification and testing must be performed by the Base Building Fire Alarm Contractor.

 

c.         Provide certification of verification on project completion.

 

d.         Installation to ULC CAN4-5524-M82.

 

e.         Verification ULC CAN4-5537.

 

f.           Sequence of operation shall be as designed for the base building.

 

5.10          Telephone / Data / Communications Raceway Systems

 

a.         Complete system shall consist of outlet box, plaster ring as required, Raceway from outlet box to terminal board in equipment room, pull wire, and coverplates on all outlets not wired by the Tenant. All wire must be FT6 rated.

 

b.         Minimum Raceway size is 19 mm (3/4"). Minimum pull wire size is 3 mm (1/8") braided nylon.

 

5.11          Wiring for Other Trades

 

a.         Provide power wiring for the mechanical trades unless noted otherwise. Provide all starters and disconnect switches as required. L.V. Controls and control wiring is provided by the mechanical contractor.

 

 

b.         Verify size, location, and electrical requirements of all mechanical equipment prior to the installation of the related electrical equipment. Maintain all clearances as required for mechanical equipment servicing.

 

c.         The electrical contractor shall provide all line voltage wiring and termination's of time clocks, controls, transformers etc. required by the mechanical contractor.

 

5.12          General

 

a.         The Landlord reserves the right, from time to time, to add to or to amend the foregoing information, procedures and regulations.

 

b.         Regulations and procedures as amended from time to time will affect any Tenant work undertaken after the amendment is issued.


 

SECTION IV

APPROVED CONTRACTORS


1.        APPROVED CONTRACTORS FOR 33 YONGE STREET

1.1              ELECTRICAL

 

 

Plan Group

Contact:          GEORGE JONES                               (416) 635-9635 ext. 385

MTI Ltd.

Contact:          MARTY MARCIL                                  (416) 815-5685

 

Power-Up                                                                    (905) 854 9758

Contact:          BOB TALBOT

 

Net Electric                                                                 (905) 737-7760

Contact:          OVE BACKMAND                              

 

Lee-Mur Electric Ltd.                                                   (416) 864-1081

Contact:          GEORGE MURRAY

1.2              MECHANICAL

Mechanical Trade Industries Ltd.                                (905) 513 1953

Contact:          STEVE CHARTRAND

 

Adelt Mechanical                                                         (905) 564 7833

Contact:          BRANDON MIRANDA

 

Black & McDonald                                                      (416) 366 2541

Contact:          ROY BRADLER

1.3              MECHANICAL (Controls)

            Mechanical Trade Industries Ltd.                                (905) 513 1953                       

            Contact:          STEVE CHARTRAND

1.4              MECHANICAL (AIR BALANCING)

 

Ace Commercial Air Test & Balancing Ltd                 (416) 727 2009

            Contact:          N/A

 

Designtest and Balance                                             (905) 886 6513

Contact:          SURRINDER SINGH

1.5              LIGHTING CONTROL SYSTEM

            Fifth Light Technologies                                              (905) 469 2142

            Contact:          TONY DABLEH

 

&